|
NAMEbelkinunv - Driver for Belkin "Universal UPS" and compatibleNOTEThis man page only documents the hardware-specific features of the belkin driver. For information about the core driver, see nutupsdrv(8).SUPPORTED HARDWAREThe belkinunv driver is known to work with the Belkin Universal UPS models F6C800-UNV and F6C120-UNV, and is expected to work with other Belkin Universal UPS models. The driver only supports serial communication, not USB.The Trust UPS and older Belkin units are not supported by this driver, and neither are the Belkin Home Office models (F6H500-SER and so forth). However, some Belkin models, such as the Regulator Pro, are supported by the belkin(8) driver, and the Home Office models are supported using the genericups(8) driver with upstype=7. SOFT SHUTDOWN WORKAROUNDOne problem with the Belkin Universal UPS is that it cannot enter a soft shutdown (shut down the load until AC power returns) unless the batteries are completely depleted. Thus, one cannot just shut off the UPS after operating system shutdown; it will not come back on when the power comes back on. Therefore, the belkinunv driver should never be used with the -k option. Instead, the -x wait option is provided as a workaround.When called with the -x wait option, belkinunv behaves as a standalone program (i.e., it does not fork into the background). It performs one simple task: it connects to the UPS, waits for AC power to return, and then exits with status 0. This is meant to be used in a shutdown script as follows: during a shutdown, after all filesystems have been remounted read-only, and just before the system would normally be halted: check /etc/killpower (or similar) to see if this shutdown was caused by upsmon(8), and if yes, call belkinunv -x wait. If AC power comes back on, belkinunv exits, and things should be arranged so that the system reboots in this case. If AC power does not come back on, the UPS will eventually run out of batteries, kill the computer’s power supply, and go into soft shutdown mode, which means everything will reboot properly when the power returns. In either case, a deadlock is avoided. In addition, if an optional integer argument is given to the -x wait option, this causes belkinunv to wait not only for AC power to be present, but also for the battery charge to reach the given level. I use this as part of my startup scripts, to ensure that the batteries are sufficiently charged before the computer continues booting. This should be put very early in the startup script, before any filesystems are mounted read/write, and before any filesystem checks are performed. Several other -x options are provided to fine-tune this behavior. See the options below for detailed descriptions. See the examples below for examples of how to use belkinunv in shutdown and startup scripts. OPTIONSSee also nutupsdrv(8) for generic options. Never use the -k option with this driver; it does not work properly.-x wait[=level] When this option is used, belkinunv does not fork
into the background, but behaves as a standalone program. It connects to the
UPS and waits until AC power is present. If level is specified, it also
waits until the battery charge reaches at least the given level in percent.
Then, and only then, belkinunv exits. In addition, while
belkinunv runs in this mode, it displays a status line with information
on the UPS status and battery level. This is intended for use in the
computer’s shutdown and startup scripts, as described under Soft
Shutdown Workaround above.
-x nohang This option only has an effect when used in conjunction
with the -x wait option. It causes belkinunv to exit if a
connection with the UPS cannot be established or is lost, instead of retrying
forever, which is the default behavior. The -x nohang option should be
used in a startup script, to ensure the computer remains bootable even if the
UPS has been disconnected during the power failure (for instance, you attached
your computer to a generator, carried it to a neighbor’s house, or
whatever).
-x flash This option only has an effect when used in conjunction
with the -x wait option. It causes the UPS load to be shut off for a
short time ("flashed") just after the AC power has returned and the
requested battery level (if any) has been attained. This is useful if slaves
are attached to this UPS; the flash will cause all of them to reboot. Note
that, due to the design of the Belkin UPS hardware, the load shutdown lasts
ca. 1—2 minutes; a shorter flash cannot be performed reliably. Also,
the computers will reboot at the scheduled time, on battery power if
necessary, even if AC power fails again in the meantime. This should not be a
problem, as your startup scripts can catch this situation.
-x silent This option only has an effect when used in conjunction
with the -x wait option. It suppresses the status line which
belkinunv would normally print.
-x dumbterm This option only has an effect when used in conjunction
with the -x wait option. It changes the way in which belkinunv
prints its status line. Normally, terminal control sequences are used to
overwrite the same line with new status information, each time the status is
updated. This may not work on all terminals. If the -x dumbterm option
is given, each status update is written on a new line.
VARIABLESbattery.charge, battery.runtimenot supported by all hardware.
battery.voltage, battery.voltage.nominal, input.frequency, input.frequency.nominal e.g. 60 for 60Hz
input.sensitivity writable: normal/medium/low
input.transfer.high writable: high transfer voltage point in V
input.transfer.low writable: low transfer voltage point in V
input.voltage, input.voltage.maximum, input.voltage.minimum, input.voltage.nominal, output.frequency, output.voltage, ups.beeper.status writable. Values: enabled/disabled/muted. This variable
controls the state of the panel beeper. Enabled means sound when the alarm is
present, disabled means never sound, and muted means the sound is temporarily
disabled until the alarm would normally stop sounding. In the muted state, the
beeper is automatically turned back on at the next event (AC failure, battery
test, etc). Also, the beeper can’t be turned off during a critical
event (low battery). Note that not all UPS models support the
"disabled" state.
ups.firmware, ups.load, ups.model, ups.power.nominal e.g. 800 for an 800VA system
ups.status a list of flags; see the status flags below.
ups.temperature not supported by all hardware.
ups.test.result, ups.delay.restart time to restart (read only)
ups.delay.shutdown time to shutdown (read only). This is always a multiple
of 60 seconds.
ups.type ONLINE/OFFLINE/LINEINT. This describes the basic layout
of this UPS (for GUI clients which want to draw an animated picture of power
flow). An offline UPS has a direct connection from AC input to AC output, and
also a connection from AC input to the battery, and from the battery to AC
output. An online UPS lacks the direct connection from AC input to AC output,
whereas a line interactive UPS lacks the connection from AC input to the
battery.
COMMANDSbeeper.enable, beeper.disable, beeper.muteEnable, disable or mute the panel beeper. Note that if
the beeper is muted, it is automatically turned back on at the next event (AC
failure, battery test, etc). Also, the beeper can’t be turned muted
during a critical event (low battery).
reset.input.minmax Reset the variables input.voltage.minimum and
input.voltage.maximum.
shutdown.reboot Shut down load immediately for about 1—2
minutes.
shutdown.reboot.graceful After 40 second delay, shut down load for about
1—2 minutes.
shutdown.stayoff Shut down load immediately and stay off. The only way it
can be turned back on is by manually pressing the front panel button.
test.battery.start, test.battery.stop Start/stop 10 second battery test.
test.failure.start, test.failure.stop Start/stop "deep" battery test.
STATUS FLAGSOBload is on battery, including during tests
OFF load is off
OL load is online
ACFAIL AC failure. Note that this refers to the AC input, and
thus it is not the same as "OB". An AC failure can occur at any
time, for instance, during a battery test, or when the UPS load is off.
OVER overload
OVERHEAT overheat
COMMFAULT UPS fault
LB low battery
CHRG charging
DEPLETED the battery is depleted. When the UPS raises this flag,
it simultaneously switches off the load.
RB replace battery
EXAMPLESHere is an example for how belkinunv should be used in a computer’s shutdown script. These commands should go in the very last part of the shutdown script, after all file systems have been mounted read-only, and just before the computer halts. Note that belkinunv must be installed in a directory which is still readable at that point.# NEAR END OF SHUTDOWN SCRIPT: # if shutdown was caused by UPS, perform Belkin UPS workaround. if [ -f /etc/killpower ] ; then echo "Waiting for AC power, or for UPS batteries to run out..." /usr/bin/belkinunv -x wait /dev/ttyS1 # we get here if the power came back on. Reboot. echo "Power is back. Rebooting..." reboot fi And here is an example of how to use belkinunv in the startup script. These commands should go near the beginning of the startup script, before any file systems are mounted read/write, and before any file system integrity checks are done. # NEAR BEGINNING OF STARTUP SCRIPT: # if we are recovering from a power failure, wait for the UPS to # charge to a comfortable level before writing anything to disk if [ -f /etc/killpower ] ; then echo "Waiting for UPS battery charge to reach 60%..." /usr/bin/belkinunv -x wait=60 -x nohang /dev/ttyS1 fi EXIT STATUSWhen used normally, belkinunv forks into the background and its diagnostics are the same as for all NUT drivers, see nutupsdrv(8).When used with the -x wait option, the exit status is normally 0. If the -x nohang option has also been specified, an exit status of 1 indicates that communication with the UPS was lost. If the -x flash option has been specified, an exit status of 2 indicates that the timed shutdown has failed. EXTRA ARGUMENTSThis driver does not support any extra settings in ups.conf(5).SEE ALSOThe core driver:nutupsdrv(8)Internet resources:•The NUT (Network UPS Tools) home page:
http://www.networkupstools.org/
•The documentation for the protocol used by this
UPS: belkin-universal-ups.html
AUTHORPeter Selinger <selinger@users.sourceforge.net>
Visit the GSP FreeBSD Man Page Interface. |