|
NAMEblazer_usb - Driver for Megatec/Q1 protocol USB based UPS equipmentNOTEThis man page only documents the hardware-specific features of the blazer driver. For information about the core driver, see nutupsdrv(8).SUPPORTED HARDWAREThe blazer driver is known to work with various UPSes from Blazer, Energy Sistem, Fenton Technologies, General Electric, Mustek and many others. The NUT compatibility table lists all the known supported models. Keep in mind, however, that other models not listed there may also be supported, but haven’t been tested.All devices with a serial interface (use the blazer_ser driver) and many with a USB interface (use the blazer_usb driver) are supported. EXTRA ARGUMENTSYou may need to override or provide defaults for some values, depending on the make and model of your UPS. The following are the ones that most likely will need changing (see ups.conf(5)):default.battery.voltage.high = value Maximum battery voltage that is reached after about 12 to
24 hours charging. If you want the driver to report a guesstimated
battery.charge, you need to specify this (see BATTERY CHARGE).
default.battery.voltage.low = value Minimum battery voltage just before the UPS automatically
shuts down. If you want the driver to report a guesstimated
battery.charge, you need to specify this (see BATTERY CHARGE).
default.battery.voltage.nominal = value, override.battery.voltage.nominal = value Some devices show a wrong nominal battery voltage (or
none at all), so you may need to override or set a default value.
override.battery.packs = value Some devices report a part of the total battery voltage.
For instance, if battery.voltage.nominal is 24 V, but it reports a
battery.voltage of around 2 V, the number of battery.packs to
correct this reading would be 12. The driver will attempt to detect this
automatically, but if this fails somehow, you may want to override this
value.
ondelay = value Time to wait before switching on the UPS (minutes). Note
that a value below 3 minutes, may cause earlier firmware versions to not
switch on automatically, so it defaults to 3 minutes. The acceptable range is
0..9999 minutes.
offdelay = value Time to wait before shutting down the UPS (seconds). This
value is truncated to units of 6 seconds (less than 60 seconds) or 60 seconds
(more than 60 seconds). Defaults to 30 seconds. The acceptable range is
12..600 seconds.
norating Some UPSes will lock up if you attempt to read rating
information from them. Setting this flag will make the driver skip this
step.
novendor Some UPSes will lock up if you attempt to read vendor
information from them. Setting this flag will make the driver skip this
step.
protocol = string Skip autodetection of the protocol to use and only use
the one specified. Supported values megatec, megatec/old,
mustek and zinto.
runtimecal = value,value,value,value Parameter used in the (optional) runtime estimation. This
takes two runtimes at different loads. Typically, this uses the runtime at
full load and the runtime at half load. For instance, if your UPS has a rated
runtime of 240 seconds at full load and 720 seconds at half load, you would
enter
runtimecal = 240,100,720,50 The first load should always be higher than the second. If you have values available for loads other than 100 and 50 % respectively, you can use those too, but keep them spaced apart as far as reasonably possible. Just don’t get too close to no load (prediction of runtime depends more on idle load for the battery then). chargetime = value The time needed to fully recharge the battery after being
fully discharged. If not specified, the driver defaults to 43200 seconds (12
hours). Only used if runtimecal is also specified.
idleload = value Minimum battery load used by the driver to estimate the
runtime. If not specified, the driver defaults to 10%. Only used if
runtimecal is also specified.
USB INTERFACE ONLYvendorid = regex, productid = regex, vendor = regex, product = regex, serial = regexSelect a specific UPS, in case there is more than one
connected via USB. Each option specifies an extended regular expression (see
regex(7)) that must match the UPS’s entire vendor/product/serial
string (minus any surrounding whitespace), or the whole 4-digit hexadecimal
code for vendorid and productid. Try -DD for finding out the strings to
match.
Examples: •-x vendor="Foo.Corporation.*"
•-x vendorid=051d* (APC)
•-x
product=".*(Smart|Back)-?UPS.*"
bus = regex Select a UPS on a specific USB bus or group of busses.
The argument is a regular expression that must match the bus name where the
UPS is connected (e.g. bus="002", bus="00[2-3]").
subdriver = string Select a serial-over-USB subdriver to use. You have a
choice between phoenix, ippon, cypress, and
krauler. When using this option, it is mandatory to also specify the
vendorid and productid.
langid_fix = value Apply the language ID workaround to the krauler
subdriver. This is mandatory for some devices to work (LDLC, Dynamix and
others). You must to provide value (0x409 or 0x4095), according to your
device entry in NUT hardware compatibility list (HCL).
UPS COMMANDSThis driver supports some instant commands (see upscmd(8)):beeper.toggle Toggle the UPS beeper. (Not available on some
hardware.)
load.on Turn on the load immediately.
load.off Turn off the load immediately (see KNOWN PROBLEMS).
shutdown.return Turn off the load and return when power is back. Uses the
timers defined by ondelay and offdelay.
shutdown.stayoff Turn off the load and remain off (see KNOWN PROBLEMS).
Uses the timer defined by offdelay.
shutdown.stop Stop a shutdown in progress.
test.battery.start.deep Perform a long battery test (Not available on some
hardware.)
test.battery.start.quick Perform a (10 second) battery test.
test.battery.start value Perform a battery test for the duration of value
minutes.
test.battery.stop Stop a running battery test (not available on some
hardware.)
BATTERY CHARGEDue to popular demand, this driver will report a guesstimated battery.charge and optionally battery.runtime, provided you specified a couple of the EXTRA ARGUMENTS listed above.If you specify both battery.voltage.high and battery.voltage.low in ups.conf(5), but don’t enter runtimecal, it will guesstimate the state of charge by looking at the battery voltage alone. This is not reliable under load, as this only gives reasonably accurate readings if you disconnect the load, let the battery rest for a couple of minutes and then measure the open cell voltage. This just isn’t practical if the power went out and the UPS is providing power for your systems. battery.voltage - battery.voltage.low battery.charge = ------------------------------------------ x 100 % battery.voltage.high - battery.voltage.low There is a way to get better readings without disconnecting the load but this requires one to keep track on how much (and how fast) current is going in- and out of the battery. If you specified the runtimecal, the driver will attempt to do this. Note however, that this heavily relies on the values you enter and that the UPS must be able to report the load as well. There are quite a couple of devices that report 0 % (or any other fixed value) at all times, in which case this obviously doesn’t work. The driver also has no way of determining the degradation of the battery capacity over time, so you’ll have to deal with this yourself (by adjusting the values in runtimecal). Also note that the driver guesses the initial state of charge based on the battery voltage, so this may be less than 100 %, even when you are certain that they are full. There is just no way to reliably measure this between 0 and 100 % full charge. This is better than nothing (but not by much). If any of the above calculations is giving you incorrect readings, you are the one that put in the values in ups.conf(5), so don’t complain with the author. If you need something better, buy a UPS that reports battery.charge and battery.runtime all by itself without the help of a NUT driver. NOTES FOR THE PREVIOUS USER OF MEGATEC DRIVERSThe blazer drivers having replaced the megatec ones, some configuration changes may be required by users switching to blazer.Part of this, the following megatec options, in ups.conf, have to be changed: battvolts You need to use default.battery.voltage.high and
default.battery.voltage.low
dtr and rts You need to use cablepower
ignoreoff This parameter can simply be discarded, since it was a
wrong understanding of the specification.
KNOWN PROBLEMSSome UPS commands aren’t supported by all models. In most cases, the driver will send a message to the system log when the user tries to execute an unsupported command. Unfortunately, some models don’t even provide a way for the driver to check for this, so the unsupported commands will silently fail.Both the load.off and shutdown.stayoff instant commands are meant to turn the load off indefinitely. However, some UPS models don’t allow this. Some models report a bogus value for the beeper status (will always be enabled or disabled). So, the beeper.toggle command may appear to have no effect in the status reported by the driver when, in fact, it is working fine. The temperature and load value is known to be bogus in some models. AUTHORSArjen de Korte <adkorte-guest at alioth.debian.org>, Alexander Gordeev <lasaine at lvk.cs.msu.su>SEE ALSOblazer_ser(8), nutupsdrv(8), upsc(8), upscmd(8), upsrw(8)Internet Resources:The NUT (Network UPS Tools) home page: http://www.networkupstools.org/The NUT HCL: http://www.networkupstools.org/stable-hcl.html
Visit the GSP FreeBSD Man Page Interface. |