NAMEoptiups - Driver for Opti-UPS (Viewsonic) UPS and Zinto D (ONLINE-USV) equipmentNOTEThis man page only documents the hardware-specific features of the optiups driver. For information about the core driver, see nutupsdrv(8).SUPPORTED HARDWAREoptiups was originally written against a PowerES 280es in nut-0.45. It was revised for nut-2.0.1 and tested against a PowerES 420E. It is expected to work with at least the PowerES, PowerPS, and PowerVS models.This driver additionally supports a Zinto D from ONLINE USV-Systeme AG because of their very similar commands, but it is unknown if it also works with other UPS from them. This driver will not work with the PowerES stock serial cable. You will need to construct your own three conductor cable: UPS 6 -> PC 3 UPS 9 -> PC 2 UPS 4 -> PC 5 The cable for Online-USV uses pin UPS 7 (not UPS 4) → PC 5. EXTRA ARGUMENTSThis driver supports the following optional settings in the ups.conf(5) file:status_only Only poll for critical status information. Without this,
optiups (and all NUT drivers) poll all sorts of information from the
UPS fairly often. It is probably not often enough to hurt anything, so this
option probably is not very useful, unless you have a flaky serial connection
or a highly loaded machine.
nowarn_noimp Does not print warnings when the UPS reports that a
variable is not implemented or not pollable. Without the option you will get a
message sent to your system logs each time NUT polls the UPS. If you specify
nowarn_noimp, this message will only be logged once.
fake_lowbatt This forces the low battery flag true. Without it, if you
want to test your UPS, you will have to unplug it and wait until the battery
drops to a low/critical voltage level before NUT will respond and power down
your system. With the flag, NUT should power down the system soon after you
pull the plug. When you are done testing, you should remove this flag.
For basic shutdown configuration testing, the command upsmon -c fsd is preferred. powerup Zinto D from ONLINE-USV cannot be identified when
switched to standby. Set this flag to allow the driver to power-up your Zinto
UPS. This will also power-up your equipment connected to the UPS!
BUGSOn the 420E, ups.serial and ups.temperature are unsupported features. This is not a bug in NUT or the NUT driver, just the way things are with this UPS.AUTHORRussell Kroll, Scott Heavner, Matthias GoeblSEE ALSOThe core driver:nutupsdrv(8)Internet resources:The NUT (Network UPS Tools) home page: http://www.networkupstools.org/